Water Hardness
The presence of Calcium and magnesium cause hardness in water

ELECTRO DEIONISATION (EDI)
Water is a natural solvent and can dissolve many elements including gases from the air. It is therefore very hard to find ‘pure’ water under natural conditions, and special techniques must be employed to remove dissolved Ions from the water.
‘Pure’ water is measured by its resistivity in MegaOhm’s with 18.2 mOhm’s (0.056µS) being ‘pure’ water. Electro DeIonisation (CEDI) is a continuous process used to produce pure and ultra-pure water using Special Ion selective membranes, Ion exchange resin and Electricity.
Electro-DeIonisation consists of Cation and Anion resins, sandwiched between layers of Cation and Anion selective membranes.
An electric current (D.C.) is passed across the bed, and the charged Cation and Anion particles flow towards their opposite charge. The resin beads help the particles to flow across the water streams.
Once the particles pass through the selective membranes, they are trapped within the resins and flushed to drain.
Excess electrical current is used to split water molecules into H and OH, which then regenerate the resins. The purified water flows through the center channel and out of the unit to be used.
To ensure quality water and reliability, good quality pre-treatment is required using Activated Carbon, Water Softeners and Reverse Osmosis. Typically a CEDI unit needs water with less than 0.1 ppm Chlorine, less than 1 ppm Hardness and less than 10uS.
Typical uses of Pure Water
If you need help or advice with any water treatment requirement, contact our team and we’ll get back to you with a tailored, compliant recommendation.